Contact Us

Suzhou Guding Electronics Co., Ltd
Tel: 0512-65138986
Fax: 0512-65776156
Email: guding88@126.com
Address: plant 5, No. 78, Yangpu Road, Suzhou Industrial Park, Suzhou Free Trade Zone, Jiangsu
Address: No. 277, North Zhonghe Road, Zhonghe District, Taiwan
Mobile: 0981733591
Fax: 886-2-22496506

< >

GDU series UPS power supply

Product parameter

GDU series UPS is an uninterruptible power supply system professionally designed and applied in telecommunications, electric power, finance, petroleum, chemical industry, aviation, railway, national defense, hospital, government, radio and television, scientific research institutions, it enterprises and other fields. It is a new generation of ups with professional quality and reliable performance


UPS features


Double conversion and on-line design are adopted to eliminate the power supply problems caused by municipal power supply and generator, and provide high-level protection for important loads.


The ups control system is integrated into a very compact cabinet, which provides an excellent equipment in terms of layout and components, with high cost performance.


It has strong anti overload ability and good anti output short-circuit current limiting ability, which can ensure the safe and reliable operation of the inverter.


GDU series inverter adopts three-phase independent inverter circuit, which can automatically adjust the voltage of each phase according to the load and power factors, and can withstand unbalanced load.


technical specifications

model

GDU-11008

GDU-11010

GDU-11012

GDU-11015

GDU-11020

GDU-11030

GDU-11040

GDU-11050

GDU-11060

capacity

8K

10K

12K

15K

20K

30K

40K

50K

60K

transport

Voltage

220Vac±25%/±380%Vac±25%

frequency

50Hz/60Hz±5Hz

Phase number

1P2W+G/3P4W+G

electric

pool

DC voltage

192Vdc

type

Sealing surface maintenance lead-acid battery

Standby time

10min (standard machine)

Charging time

Charge to more than 90% in 10 hours

Voltage

220Vac

transport

Out

Voltage stability

±1%

frequency

50Hz±0.3%

Phase number

1P2W+G

power factor

Lag 0.8-1

Dynamic response

electric

pool

DC voltage

192Vdc

type

Sealing surface maintenance lead-acid battery

Standby time

10min (standard machine)

Charging time

Charge to more than 90% in 10 hours

Voltage

220Vac

transport

Out

Voltage stability

±1%

frequency

50Hz±0.3%

Phase number

1P2W+G

power factor

Lag 0.8-1

Dynamic response

CPU digital display, self detection: model, input and output voltage, frequency, output current, UPS operating temperature, load utilization percentage.

Historical records and analysis of power anomalies

alarm system

Three stage warning: 1 Call every 4 seconds when the mains power is interrupted; 4. The battery will sound low every 2 seconds; 3. The buzzer will sound in case of overload

Short circuit protection

Stop inverter output instead of bypass

work

environment

temperature

0℃-43℃

relative humidity

10% - 90% (no condensation)

Dimension (W) × D × H)mm

three hundred and eighty × five hundred and ninety-five × nine hundred and fifty-five

four hundred and sixty × six hundred and fifty × one thousand one hundred and sixty

six hundred and fifty × eight hundred × one thousand six hundred and ninety

Weight (kg)

Net weight

85

155

170

190

265

320

410

480

550

Gross weight

105

185

190

215

295

355

450

540

610



technical parameter

topological structure

DC / DC, DC / AC double conversion, input and output electrical isolation, real online UPS

input voltage

three-phase380/400/415V±20%

frequency

50/60Hz±10%Automatic tracking selection

Source test PF

0.8-0.95 (optional)

Input step

The slow start time of UPS input current rising from zero to rated value is 15 seconds (10-255 seconds can be adjusted)

output voltage

Three phase series: 380 / 400 / 145v ± 1% (± 0.5% optional), and the three-phase phase difference is within 120 °± 1 °

Single phase series: 220 / 230 / 240V ± 1% (± 0.5% optional)

output frequency

Synchronization with mains power: 50 / 60Hz ± 0.5,1,1.5,2hz (adjustable), battery operation: 50 / 60Hz = 0.01%

Output waveform

Pure sine wave, linear load thd ≤ 1%, nonlinear load thd ≤ 2%

Load capacity

Inverter: 125% load for 15 minutes; 150% load for 60 seconds; Static bypass: 20ms under 2000% load; 200% load for 1 minute; Continuous operation at 150% load

Load characteristics

The load crest factor is greater than 3:1, three-phase independent voltage stabilization, and long-term operation with 100% unbalanced load is allowed

dynamic response

100% load step, the voltage change is within ± 2%, and it will recover to within ± 1% within 10ms

Parallel backup

Independent bypass input circuit, variable machine in parallel, mutual master / slave backup and parallel machine

Parallel redundancy

10 sets can be operated directly in parallel, independent parallel operation, load sharing, and N + 1 redundancy

Source test PF

0.8-0.95 (optional)

Input step

The slow start time of UPS input current rising from zero to rated value is 15 seconds (10-255 seconds can be adjusted)

output voltage

Three phase series: 380 / 400 / 145v ± 1% (± 0.5% optional), and the three-phase phase difference is within 120 °± 1 °

Single phase series: 220 / 230 / 240V ± 1% (± 0.5% optional)

output frequency

Synchronization with mains power: 50 / 60Hz ± 0.5,1,1.5,2hz (adjustable), battery operation: 50 / 60Hz = 0.01%

Output waveform

Pure sine wave, linear load thd ≤ 1%, nonlinear load thd ≤ 2%

Load capacity

Inverter: 125% load for 15 minutes; 150% load for 60 seconds; Static bypass: 20ms under 2000% load; 200% load for 1 minute; Continuous operation at 150% load

Load characteristics

The load crest factor is greater than 3:1, three-phase independent voltage stabilization, and long-term operation with 100% unbalanced load is allowed

dynamic response

100% load step, the voltage change is within ± 2%, and it will recover to within ± 1% within 10ms

Parallel backup

Independent bypass input circuit, variable machine in parallel, mutual master / slave backup and parallel machine

Protection level

IP20-IP42,IEC529/EN60529

colour

International Raul color code ral7035 (International gray) plastic spraying


Installation configuration parameter table

GDU series 10-120kva (three-phase input and three-phase output)

UPScapacity

10KVA

15KVA

20KVA

30KVA

40KVA

50KVA

60KVA

80KVA

100KVA

120KVA

input voltage

380 / 400 / 415vac (three-phase four wire)

DC voltage

384VDC

output voltage

380 / 400 / 415vac (three-phase four wire)

Inverter efficiency

93%

93%

93%

93%

94%

94%

94%

95%

95%

95%

Rectifier efficiency

95%

95%

95%

96%

95%

96%

97%

97%

97%

97%

Overall efficiency

92%

92%

92%

92%

93%

93%

93%

93%

93%

93%

Audible noise

<58dBA

<58dBA

<58dBA

<58dBA

<59dBA

<59dBA

<59dBA

<60dBA

<60dBA

<60dBA

Host size

Width 620 × High 1470 × Depth 640 (mm)

Width 820 × High 1470 × Depth 640 (mm)

Net weight of main engine

310KG

315KG

330KG

345KG

440KG

480KG

510KG

610KG

625KG

650KG


GDU series 140-800kva (three-phase input and three-phase output)


UPS capacity

140KVA

160KVA

200KVA

250KVA

300KVA

350KVA

400KVA

500KVA

600KVA

800KVA

input voltage

380/400/415VAC(Three phase four wire)

DC voltage

384VDC

output voltage

380/400/415VAC(Three phase four wire)

Inverter efficiency

95%

95%

95%

95%

96%

96%

96%

96%

96%

96%

Rectifier efficiency

97%

97%

97%

97%

98%

98%

98%

98%

98%

98%

Overall efficiency

93%

93%

93%

93%

94%

94%

94%

94%

94%

94%

Audible noise

<62dBA

<62dBA

<63dBA

<63dBA

<63dBA

<63dBA

<63dBA

<63dBA

<63dBA

<63dBA

Host size

1000 wide × 1750 high × Depth 910 (mm)

Width 1640 × High 1850 × Depth 910 (mm)

2400 wide × High 2020 × Depth 950 (mm)

Net weight of main engine

1030KG

1080KG

1230KG

1430KG

1600KG

1680KG

1800KG

2000KG

2200KG

3000KG


GDUseries10-100KVA(three-phase input and three-phase output))


UPScapacity

10KVA

15KVA

20KVA

25KVA

30KVA

40KVA

50KVA

60KVA

80KVA

100KVA

input voltage

380/400/415VAC(Three phase four wire)

DC voltage

384VDC

output voltage

220/230/240VAC(single-phase)

Inverter efficiency

94%

94%

94%

94%

94%

95%

95%

95%

95%

95%

Rectifier efficiency

97%

97%

97%

97%

98%

98%

98%

98%

98%

98%

Overall efficiency

93%

93%

93%

93%

93%

94%

94%

94%

94%

94%

Audible noise

<58dBA

<58dBA

<59dBA

<59dBA

<59dBA

<60dBA

<60dBA

<60dBA

<62dBA

<62dBA

Host size

Width 620 × 1200 high × Depth 840 (mm)

Width 820 × High 1470 × Depth 840 (mm)

1000 wide × 1750 high × Depth 910 (mm)

Net weight of main engine

220KG

235KG

270KG

275KG

285KG

415KG

450KG

480KG

630KG

680KG


Special specifications can be customized



Previous:Nothing