model |
GDU-11008 |
GDU-11010 |
GDU-11012 |
GDU-11015 |
GDU-11020 |
GDU-11030 |
GDU-11040 |
GDU-11050 |
GDU-11060 |
|||||
capacity |
8K |
10K |
12K |
15K |
20K |
30K |
40K |
50K |
60K |
|||||
transport 入 |
Voltage |
220Vac±25%/±380%Vac±25% |
||||||||||||
frequency |
50Hz/60Hz±5Hz |
|||||||||||||
Phase number |
1P2W+G/3P4W+G |
|||||||||||||
electric pool |
DC voltage |
192Vdc |
||||||||||||
type |
Sealing surface maintenance lead-acid battery |
|||||||||||||
Standby time |
10min (standard machine) |
|||||||||||||
Charging time |
Charge to more than 90% in 10 hours |
|||||||||||||
Voltage |
220Vac |
|||||||||||||
transport Out |
Voltage stability |
±1% |
||||||||||||
frequency |
50Hz±0.3% |
|||||||||||||
Phase number |
1P2W+G |
|||||||||||||
power factor |
Lag 0.8-1 |
|||||||||||||
Dynamic response |
||||||||||||||
electric pool |
DC voltage |
192Vdc |
||||||||||||
type |
Sealing surface maintenance lead-acid battery |
|||||||||||||
Standby time |
10min (standard machine) |
|||||||||||||
Charging time |
Charge to more than 90% in 10 hours |
|||||||||||||
Voltage |
220Vac |
|||||||||||||
transport Out |
Voltage stability |
±1% |
||||||||||||
frequency |
50Hz±0.3% |
|||||||||||||
Phase number |
1P2W+G |
|||||||||||||
power factor |
Lag 0.8-1 |
|||||||||||||
Dynamic response |
CPU digital display, self detection: model, input and output voltage, frequency, output current, UPS operating temperature, load utilization percentage. Historical records and analysis of power anomalies |
|||||||||||||
alarm system |
Three stage warning: 1 Call every 4 seconds when the mains power is interrupted; 4. The battery will sound low every 2 seconds; 3. The buzzer will sound in case of overload |
|||||||||||||
Short circuit protection |
Stop inverter output instead of bypass |
|||||||||||||
work environment |
temperature |
0℃-43℃ |
||||||||||||
relative humidity |
10% - 90% (no condensation) |
|||||||||||||
Dimension (W) × D × H)mm |
three hundred and eighty × five hundred and ninety-five × nine hundred and fifty-five |
four hundred and sixty × six hundred and fifty × one thousand one hundred and sixty |
six hundred and fifty × eight hundred × one thousand six hundred and ninety |
|||||||||||
Weight (kg) |
Net weight |
85 |
155 |
170 |
190 |
265 |
320 |
410 |
480 |
550 |
||||
Gross weight |
105 |
185 |
190 |
215 |
295 |
355 |
450 |
540 |
610 |
technical parameter
topological structure |
DC / DC, DC / AC double conversion, input and output electrical isolation, real online UPS |
input voltage |
three-phase380/400/415V±20% |
frequency |
50/60Hz±10%Automatic tracking selection |
Source test PF |
0.8-0.95 (optional) |
Input step |
The slow start time of UPS input current rising from zero to rated value is 15 seconds (10-255 seconds can be adjusted) |
output voltage |
Three phase series: 380 / 400 / 145v ± 1% (± 0.5% optional), and the three-phase phase difference is within 120 °± 1 ° Single phase series: 220 / 230 / 240V ± 1% (± 0.5% optional) |
output frequency |
Synchronization with mains power: 50 / 60Hz ± 0.5,1,1.5,2hz (adjustable), battery operation: 50 / 60Hz = 0.01% |
Output waveform |
Pure sine wave, linear load thd ≤ 1%, nonlinear load thd ≤ 2% |
Load capacity |
Inverter: 125% load for 15 minutes; 150% load for 60 seconds; Static bypass: 20ms under 2000% load; 200% load for 1 minute; Continuous operation at 150% load |
Load characteristics |
The load crest factor is greater than 3:1, three-phase independent voltage stabilization, and long-term operation with 100% unbalanced load is allowed |
dynamic response |
100% load step, the voltage change is within ± 2%, and it will recover to within ± 1% within 10ms |
Parallel backup |
Independent bypass input circuit, variable machine in parallel, mutual master / slave backup and parallel machine |
Parallel redundancy |
10 sets can be operated directly in parallel, independent parallel operation, load sharing, and N + 1 redundancy |
Source test PF |
0.8-0.95 (optional) |
Input step |
The slow start time of UPS input current rising from zero to rated value is 15 seconds (10-255 seconds can be adjusted) |
output voltage |
Three phase series: 380 / 400 / 145v ± 1% (± 0.5% optional), and the three-phase phase difference is within 120 °± 1 ° Single phase series: 220 / 230 / 240V ± 1% (± 0.5% optional) |
output frequency |
Synchronization with mains power: 50 / 60Hz ± 0.5,1,1.5,2hz (adjustable), battery operation: 50 / 60Hz = 0.01% |
Output waveform |
Pure sine wave, linear load thd ≤ 1%, nonlinear load thd ≤ 2% |
Load capacity |
Inverter: 125% load for 15 minutes; 150% load for 60 seconds; Static bypass: 20ms under 2000% load; 200% load for 1 minute; Continuous operation at 150% load |
Load characteristics |
The load crest factor is greater than 3:1, three-phase independent voltage stabilization, and long-term operation with 100% unbalanced load is allowed |
dynamic response |
100% load step, the voltage change is within ± 2%, and it will recover to within ± 1% within 10ms |
Parallel backup |
Independent bypass input circuit, variable machine in parallel, mutual master / slave backup and parallel machine |
Protection level |
IP20-IP42,IEC529/EN60529 |
colour |
International Raul color code ral7035 (International gray) plastic spraying |
Installation configuration parameter table
GDU series 10-120kva (three-phase input and three-phase output)
UPScapacity |
10KVA |
15KVA |
20KVA |
30KVA |
40KVA |
50KVA |
60KVA |
80KVA |
100KVA |
120KVA |
input voltage |
380 / 400 / 415vac (three-phase four wire) |
|||||||||
DC voltage |
384VDC |
|||||||||
output voltage |
380 / 400 / 415vac (three-phase four wire) |
|||||||||
Inverter efficiency |
93% |
93% |
93% |
93% |
94% |
94% |
94% |
95% |
95% |
95% |
Rectifier efficiency |
95% |
95% |
95% |
96% |
95% |
96% |
97% |
97% |
97% |
97% |
Overall efficiency |
92% |
92% |
92% |
92% |
93% |
93% |
93% |
93% |
93% |
93% |
Audible noise |
<58dBA |
<58dBA |
<58dBA |
<58dBA |
<59dBA |
<59dBA |
<59dBA |
<60dBA |
<60dBA |
<60dBA |
Host size |
Width 620 × High 1470 × Depth 640 (mm) |
Width 820 × High 1470 × Depth 640 (mm) |
||||||||
Net weight of main engine |
310KG |
315KG |
330KG |
345KG |
440KG |
480KG |
510KG |
610KG |
625KG |
650KG |
GDU series 140-800kva (three-phase input and three-phase output)
UPS capacity |
140KVA |
160KVA |
200KVA |
250KVA |
300KVA |
350KVA |
400KVA |
500KVA |
600KVA |
800KVA |
input voltage |
380/400/415VAC(Three phase four wire) |
|||||||||
DC voltage |
384VDC |
|||||||||
output voltage |
380/400/415VAC(Three phase four wire) |
|||||||||
Inverter efficiency |
95% |
95% |
95% |
95% |
96% |
96% |
96% |
96% |
96% |
96% |
Rectifier efficiency |
97% |
97% |
97% |
97% |
98% |
98% |
98% |
98% |
98% |
98% |
Overall efficiency |
93% |
93% |
93% |
93% |
94% |
94% |
94% |
94% |
94% |
94% |
Audible noise |
<62dBA |
<62dBA |
<63dBA |
<63dBA |
<63dBA |
<63dBA |
<63dBA |
<63dBA |
<63dBA |
<63dBA |
Host size |
1000 wide × 1750 high × Depth 910 (mm) |
Width 1640 × High 1850 × Depth 910 (mm) |
2400 wide × High 2020 × Depth 950 (mm) |
|||||||
Net weight of main engine |
1030KG |
1080KG |
1230KG |
1430KG |
1600KG |
1680KG |
1800KG |
2000KG |
2200KG |
3000KG |
GDUseries10-100KVA(three-phase input and three-phase output))
UPScapacity |
10KVA |
15KVA |
20KVA |
25KVA |
30KVA |
40KVA |
50KVA |
60KVA |
80KVA |
100KVA |
input voltage |
380/400/415VAC(Three phase four wire) |
|||||||||
DC voltage |
384VDC |
|||||||||
output voltage |
220/230/240VAC(single-phase) |
|||||||||
Inverter efficiency |
94% |
94% |
94% |
94% |
94% |
95% |
95% |
95% |
95% |
95% |
Rectifier efficiency |
97% |
97% |
97% |
97% |
98% |
98% |
98% |
98% |
98% |
98% |
Overall efficiency |
93% |
93% |
93% |
93% |
93% |
94% |
94% |
94% |
94% |
94% |
Audible noise |
<58dBA |
<58dBA |
<59dBA |
<59dBA |
<59dBA |
<60dBA |
<60dBA |
<60dBA |
<62dBA |
<62dBA |
Host size |
Width 620 × 1200 high × Depth 840 (mm) |
Width 820 × High 1470 × Depth 840 (mm) |
1000 wide × 1750 high × Depth 910 (mm) |
|||||||
Net weight of main engine |
220KG |
235KG |
270KG |
275KG |
285KG |
415KG |
450KG |
480KG |
630KG |
680KG |
Special specifications can be customized